Binary Input Settings; Network1 Address Settings; Network2 Address Settings; Hmi Port Address Settings - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
3.1.2

Binary input settings

Table 8: Binary input settings
Parameter
Slot specific threshold
Slot specific hysteresis
Input threshold voltage
Input threshold hysteresis
Input osc. level
Input osc. hyst
3.1.3

Network1 address settings

Table 9: Non group settings
Parameter
Values (Range)
IP address
Subnet mask
Default gateway
Mac address
3.1.4

Network2 address settings

Table 10: Non group settings
Parameter
Values (Range)
Enable
0=False
1=True
IP address
Subnet mask
Default gateway
Mac address
3.1.5

HMI port address settings

58
Values (Range)
Unit
0=False
1=True
0=False
1=True
16...176
Vdc
10...50
%
2...50
events/s 1
2...50
events/s 1
Unit
Unit
Step
Default
0=False
0=False
2
16
2
10
30
10
Step
Default
192.168.2.10
255.255.255.0
192.168.2.1
XX-XX-XX-XX-XX-XX Mac address for
Step
Default
0=False
192.168.3.10
255.255.255.0
0.0.0.0
XX-XX-XX-XX-XX-XX Mac address for
1MRS759142 F
Description
Use slot specific binary input
voltage threshold
Use slot specific binary input
voltage hysteresis
Global binary input threshold
for all slots
Global binary input hysteresis
for all slots
Binary input oscillation sup-
pression threshold
Binary input oscillation sup-
pression hysteresis
Description
IP address for Net-
work1
Subnet mask for
Network1
Default gateway for
Network1
Network1
Description
Enable Network2 IP
address
IP address for Net-
work2
Subnet mask for
Network2
Default gateway for
Network2 (only in-
use if NW1 GW =
0.0.0.0)
Network2
REX640
Technical Manual

Advertisement

Table of Contents
loading