1MRS759142 F
The operation of PREVPTOC can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
Figure 475: Functional module diagram
Level detector
The level detector compares the negative-sequence current to the set
the I
to the timer module.
Timer
Once activated, the timer activates the START output. When the operation timer
has reached the set
the fault disappears before the module operates, the reset timer is activated. If the
reset timer reaches the value of 200 ms, the operation timer resets and the START
output is deactivated.
The timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is
available in the monitored data view.
4.4.4.6
Application
The rotation of a motor in the reverse direction is not a desirable operating
condition. When the motor drives fans and pumps, for example, and the rotation
direction is reversed due to a wrong phase sequence, the driven process can be
disturbed and the flow of the cooling air of the motor can become reversed too.
With a motor designed only for a particular rotation direction, the reversed rotation
direction can lead to an inefficient cooling of the motor due to the fan design.
In a motor, the value of the negative-sequence component of the phase currents is
very negligible when compared to the positive-sequence component of the current
during a healthy operating condition of the motor. But when the motor is started
with the phase connections in the reverse order, the magnitude of I
So whenever the value of I
rotation direction and provides an operating signal that disconnects the motor
from the supply.
4.4.4.7
Signals
REX640
Technical Manual
I
I3P
BLOCK
value exceeds the set
2
Operate delay time value, the OPERATE output is activated. If
Timer
Level
2
detector
Start value , the level detector sends an enabling signal
exceeds the start value, the function detects the reverse
2
Protection functions
OPERATE
t
START
Start value . If
is very high.
2
839