ABB RELION REX640 Technical Manual page 836

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Figure 473: Three-phase current quantities during the broken conductor fault in
phase A with the ratio of negative-sequence and positive-sequence currents
4.4.3.7
Signals
PDNSPTOC Input signals
Table 755: PDNSPTOC Input signals
Name
I3P
BLOCK
PDNSPTOC Output signals
Table 756: PDNSPTOC Output signals
Name
OPERATE
START
4.4.3.8
PDNSPTOC Settings
Table 757: PDNSPTOC Group settings (Basic)
Parameter
Values (Range)
Start value
10...100
Operate delay time
100...30000
836
Type
SIGNAL
BOOLEAN
Type
BOOLEAN
BOOLEAN
Unit
Step
%
1
ms
1
Default
Description
-
Three-phase currents
0=False
Block signal for acti-
vating the blocking
mode
Description
Operate
Start
Default
10
100
1MRS759142 F
Description
Start value
Operate delay time
REX640
Technical Manual