Protection functions
Condition
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.5.7.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of OEPVPH can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
I3P
U3P
BLOCK
Figure 495: Functional module diagram
U/f calculation
This module calculates the U/f ratio, that is, the excitation level from the internal
induced voltage (E) and frequency. The actual measured voltage (U
from the internal induced voltage (E), a value the equipment has to withstand. This
voltage compensation is based on the load current (I
) of the equipment. The leakage reactance of the transformer or generator is set
leak
through the
The internal induced voltage (E) is calculated from the measured voltage. The
settings
currents are to be used. If the
or "phase-to-phase", the
phases or phase-to-phase voltages ("A or AB", "B or BC" and "C or CA") and currents
are to be used for the calculation of the induced voltage.
886
I_A
I_B
I_C
I
1
U_A_AB
U/f
calculation
U_B_BC
U_C_CA
U
1
F
Leakage React setting in percentage of the Z base.
Voltage selection and Phase supervision determine which voltages and
Phase supervision setting is used for determining which
Description
to
Phase selection "1", "2" or "3") if Voltage
selection is set to "phase-to-phase".
The function requires that all three voltage
channels are connected if
set to "pos sequence".
Operation setting. The
Timer
Level
detector
Blocking
logic
Voltage selection setting is set to "phase-to-earth"
1MRS759142 F
Voltage selection is
OPERATE
t
START
BLK_RESTART
t
COOL_ACTIVE
) deviates
m
) and the leakage reactance (X
L
Technical Manual
REX640