ABB RELION REX640 Technical Manual page 438

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
I
Figure 251: Rogowski coil measurement arrangement
It is also possible to feed shaft current, measured with CT, directly to the relay
current input. Proper signal levels need to be ensured for reaching acceptable
operation accuracy.
Setting
The current level that causes damage to bearings depends on the contact surface of
the bearings. Current densities over 0.1 A/mm
can be generalized so, that currents over 1 A can be considered harmful. Therefore,
the recommended setting for
0.25 A. Both values are set in primary amperes.
4.1.12.7
Signals
GSLPTOC Input signals
Table 496: GSLPTOC Input signals
Name
ISHFT
BLOCK
GSLPTOC Output signals
Table 497: GSLPTOC Output signals
Name
OPERATE
START
ALARM
438
Rogowski
Integrator box
coil
Alarm start value and Operate start value
Type
SIGNAL
BOOLEAN
Amplifier
2
start to damage the bearings. This
Operate start value is 0.5 A and for Alarm start value
Default
-
0=False
Type
BOOLEAN
BOOLEAN
BOOLEAN
1MRS759142 F
Protection relay
I>
Description
Analog input
Block signal for all bi-
nary outputs
Description
Operate
Start
Alarm
REX640
Technical Manual