Protection functions
Figure 485: Behavior of different IDMT reset modes. Operate signal is based on
settings Type of reset curve = "Def time reset" and Type of time reset= "Freeze Op
timer". The effect of other reset modes is also presented
The
The
time for IDMT. The setting is applicable only when the IDMT curves are used.
The Timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is
available in the Monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the BLOCK input and the global setting in Configuration > System >
Blocking mode which selects the blocking mode. The BLOCK input can be controlled
862
Time multiplier setting is used for scaling the IDMT operate times.
Minimum operate time setting parameter defines the minimum desired operate
Minimum operate time setting should be used with care because the
The
operation time is according to the IDMT curve, but always at least the
Minimum operate time setting. For more information, see
value of the
Chapter 11.3.2 IDMT curves for undervoltage protection
1MRS759142 F
in this manual.