ABB RELION REX640 Technical Manual page 642

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Parameter
Values (Range)
CB delay Comp
0...200
4.2.10.8
IFPTOC Monitored data
Table 643: IFPTOC Monitored data
Name
Type
FLT_CURRENT
FLOAT32
FLT_CURR_RMS
FLOAT32
TCH_VOLTAGE
FLOAT32
TCH_VOLT_RMS
FLOAT32
RF
FLOAT32
FAULT_PHASE
Enum
TR_RIS_COMP
FLOAT32
TR_REACT_COMP
FLOAT32
NON_Q_HARMON
INT32
START_DUR
FLOAT32
OPERATE_TIME
FLOAT32
TIME_TO_OPER
FLOAT32
642
Unit
Step
ms
1
Values (Range)
0.00...6000.00
0.00...6000.00
0.00...440000.00
0.00...440000.00
0.0...20000.0
-5=No fault
-4=ABCG Fault
-3=CAG Fault
-2=BCG Fault
-1=ABG Fault
1=AG Fault
2=BG Fault
3=CG Fault
4=AB Fault
5=BC Fault
6=CA Fault
7=ABC Fault
-6000.0...6000.0
-6000.0...6000.0
0...127
0.00...100.00
0.000...7200.000
0.000...7200.000
Default
0
Unit
Description
A
Magnitude of estima-
ted earth-fault current
[primary amperes] (fun-
damental freq.)
A
Magnitude of estima-
ted earth-fault current
[primary amperes], rms
(incl. harmonics)
V
Magnitude of estima-
ted touch voltage (fun-
damental freq.) [pri-
mary volts]
V
Magnitude of estima-
ted touch voltage [pri-
mary volts], rms (incl.
harmonics)
ohm
Fault point resistance in
primary ohms
Faulted phase
A
Magnitude of transi-
ent real part of resid-
ual current, in primary
amperes (fundamental
freq.)
A
Magnitude of transient
imaginary part of resid-
ual current, in primary
amperes (fundamental
freq.)
Non qualified harmon-
ics in binary coded for-
mat
%
Ratio of start time / op-
erate time
s
Actual operate time
s
Time left to operate
1MRS759142 F
Description
continuous earth
fault.
Delay compensa-
tion for circuit-
breaker operate
time
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents