ABB RELION REX640 Technical Manual page 86

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
Table 35: Secondary IP address parameters
Parameter
Configuration/Communication/Ether-
net/Network 2 address/ Enable
Configuration/Communication/Ether-
net/Network 2 address/IP address
Configuration/Communication/Ether-
net/Network 2 address/IP address
Configuration/Communication/Ether-
net/Network 2 address/MAC address
The IP address for Network 2 is disabled by default settings, and all Ethernet
ports are assigned to the same IP address used in the Network 1 address menu
Configuration > Communication > Ethernet > Network 1. If Network 2 is taken
into use by the setting Enable="True" (requires reboot), the interlink port X3 of the
COM module is assigned to this second network, using the IP address and subnet
parameters in the Network 2 address menu Configuration > Communication >
Ethernet > Network 2 address.
86
If the Network 2 interface is enabled, PTP time synchronization and SMV/
GOOSE multicast are disabled for that port.
The secondary IP setting must not collide with the primary Network 1 IP
address or LHMI IP address, otherwise the secondary IP address is not
taken into use.
Options
False (default)
TRUE
0.0.0.0
0.0.0.0
xx-xx-xx-xx-xx-xx
1MRS759142 F
Description
Network 2 disabled
Network 2 enabled
IP address for Net-
work 2
Subnet address for
Network 2
MAC address for Net-
work 2
REX640
Technical Manual