ABB RELION REX640 Technical Manual page 878

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
An appropriate value for the setting parameter
3 percent of U
depends on the application. If the NSPTOV operation is used as backup protection,
the operate time should be set in accordance with the operate time of NSPTOC used
as main protection. If the NSPTOV operation is used as main protection, the operate
time should be approximately one second.
4.5.5.7
Signals
NSPTOV Input signals
Table 823: NSPTOV Input signals
Name
U3P
BLOCK
NSPTOV Output signals
Table 824: NSPTOV Output signals
Name
OPERATE
START
4.5.5.8
NSPTOV Settings
Table 825: NSPTOV Group settings (Basic)
Parameter
Values (Range)
Start value
0.010...1.000
Operate delay time
40...120000
Table 826: NSPTOV Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 827: NSPTOV Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
878
. A suitable value for the setting parameter
n
Type
SIGNAL
BOOLEAN
Type
BOOLEAN
BOOLEAN
Unit
Step
xUn
0.001
ms
1
Unit
Step
Unit
Step
ms
1
Voltage start value is approximately
Operate delay time
Default
Description
-
Three-phase voltages
0=False
Block signal for acti-
vating the blocking
mode
Description
Operate
Start
Default
0.030
40
Default
1=on
Default
20
1MRS759142 F
Description
Start value
Operate delay time
Description
Operation Off / On
Description
Reset delay time