3.22.5.2
Functionality
The real equal comparator function EQR compares the real input REAL_IN1 with the
real input REAL_IN2 and activates the binary output OUT if REAL_IN1 is within the
region of REAL_IN2 + TOLR and REAL_IN2 –TOLR, that is, if REAL_IN1 ≥ (REAL_IN2
– TOLR) and REAL_IN1 ≤ (REAL_IN2 + TOLR), OUT = 1, else OUT = 0.
If inputs REAL_IN1 or REAL_IN2 are outside the range, then OUT is set to 0.
REAL_IN2+TOLR
REAL_IN2-TOLR
Figure 177: Region of EQR comparison
3.22.5.3
Signals
Table 323: EQR Input signals
Name
REAL_IN1
REAL_IN2
TOLR
Table 324: EQR Output signals
Name
OUT
REX640
Technical Manual
REAL_IN2
EQR requires a positive value for TOLR, otherwise it may not function
properly. The TOLR value can be set using SETRGAPC.
EQR function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
closely varying values.
Type
FLOAT32
FLOAT32
FLOAT32
Type
BOOLEAN
Equal region
Equal region
Default
0
0
0
Description
Output value
Basic functions
Description
Real input 1
Real input 2
Tolerance for compar-
ison