Protection functions
4.5.10.10
Technical data
Table 878: PHVPTOV Technical data
Characteristic
Operation accuracy
Reset ratio
Operate time accuracy in definite time mode ±1.0 % of the set value or ±20 ms
4.6
Frequency protection
4.6.1
Frequency protection FRPFRQ (ANSI 81)
4.6.1.1
Identification
Function description
Frequency protection
4.6.1.2
Function block
Figure 513: Function block
4.6.1.3
Functionality
The frequency protection function FRPFRQ is used to protect network components
against abnormal frequency conditions.
The function provides basic overfrequency, underfrequency and frequency rate-of-
change protection. Additionally, it is possible to use combined criteria to achieve
even more sophisticated protection schemes for the system.
The function contains a blocking functionality. It is possible to block function
outputs, timer or the function itself.
920
Value
Depending on the frequency of the measured
voltage: f
n
±1.5 % of the set value or ±0.002 × U
Depends on the set
IEC 61850
IEC 60617
identification
identification
FRPFRQ
f>/f<,df/dt
1MRS759142 F
n
Relative hysteresis
ANSI/IEEE C37.2
device number
81
REX640
Technical Manual