Protection functions
fault appears, creating a rotor winding interturn fault and causing severe magnetic
imbalance and heavy rotor vibrations that soon lead to a severe damage.
Therefore, it is essential that any occurrence of an insulation failure is detected
and that the machine is disconnected as soon as possible. Normally, the device is
tripped after a short time delay.
A 50/60 Hz voltage is injected via the injection device REK 510 to the rotor field
winding circuit of the synchronous machine as shown in
voltage is 100 V AC via the coupling capacitors. A coupling capacitor prevents a DC
current leakage through the injection device.
Figure 298: Principle of the rotor earth-fault protection with the current injection
device
The auxiliary AC voltage forms a small charging current I
capacitors, resistances of the brushes and the leakage capacitance between the
field circuit and earth. The field-to-earth capacitance C
resulting current to an extent which is a few milliamperes during normal no-fault
operating conditions.
If an earth fault arises in the rotor field circuit, this current increases and can reach a
level of 130 mA at a fully developed earth fault (fault resistance R
capacitor C
device REK 510 then amplifies this current with the ratio of 1:10 to a measurable
level. MREFPTOC is used to measure this current.
An example of the measured curves with various field-to-earth leakage capacitance
values is given in
It is recommended that the alarm and operation stages of MREFPTOC are both
used. The alarm stage for giving an indication for weakly developed earth faults
with a start value setting corresponds to a 10 kΩ fault resistance with a 10-second
delay. The operation stage for a protection against fully developed earth faults with
a start value setting corresponds to a 1...2 kΩ fault resistance with a 0.5-second
delay.
518
= 2μF is used). The integrated current transformer of the injection
1
Figure 299
.
The current setting values corresponding to the required operating fault
resistances can be tested by connecting an adjustable fault simulating
resistor between the excitation winding poles and the earth. Whether
only one of the coupling capacitors or both should be used in a parallel
connection should be determined on a case-by-case basis, taking into
consideration the consequences of a possibly excessive current at a
direct earth fault.
1MRS759142 F
Figure 298
. The injected
to flow via the coupling
1
affects the level of the
E
= 0, one coupling
E
Technical Manual
REX640