ABB RELION REX640 Technical Manual page 575

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Estimated stabilized fundamental frequency residual current
set Min operate current level, which is applied in current magnitude threshold
supervision, and which is further defined with setting Operating quantity
(available options are "Adaptive", "Amplitude" and "Resistive").
In the "Transient EF" mode, the START output is activated immediately when start
conditions are met.
release
Operate
Reset timer
START
OPERATE
Figure 331: Operation in "Transient EF" mode
Blocking logic
There are three operation modes in the blocking functionality. The operation
modes are controlled by the BLOCK input and the global setting Configuration >
System > Blocking mode which selects the blocking mode. The BLOCK input can be
REX640
Technical Manual
Uo
Io
GFC
timer
Reset delay time
When operation mode "Transient EF" is selected,
should be set to "Resistive" and
Tilt angle should be 10 degrees especially if the residual current is
value.
measured with Holmgreen (sum) connection of phase current CTs.
Protection functions
Operate delay time
Operating quantity
Min operate current to the minimum
1
I
exceeds the
o stab
575