ABB RELION REX640 Technical Manual page 631

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
The IFPTOC has inbuild directional transient detector module for detecting earth-
fault transients. Transient detector module is used to count the number of
transients during an earth fault to discriminate intermittent earth fault from
continuous earth fault.
Internal start of intermittent earth-fault module is obtained when the presence of
earth fault is indicated (EF_IND), it's validity is confirmed (VALID_EF) and at least
one transient is detected in the protected feeder. Whenever a fault transient is
detected, this is indicated with the PEAK_IND output.
When the number of detected transients reaches the
INTR_EF output is activated. Activation of INTR_EF output indicates detection of a
restriking or intermittent earth fault in the protected feeder.
Figure 358: Illustration of operation of intermittent earth-fault module. Setting Intr
EF counter Lim = 3
When a required number of intermittent earth-fault transients set with the
EF counter Lim setting are detected without the function being reset (depends
on the drop-off time set with the setting
single-phase earth fault in the protected feeder is confirmed (activation of EF_IND
and VALID_EF outputs), the START and ST_INTR_EF outputs are activated. The
OPERATE and OP_INTR_EF outputs are activated when operate delay time
operate time has elapsed (from fault beginning), required number of transients
exceeds setting
REX640
Technical Manual
Transient detector module counts the number of transients during an
earth fault both in faulty and healthy feeders. Detection of transients is
indicated with PEAK_IND output.
Intr EF counter Lim (so actually for operation there must be Intr
Intr EF counter Lim setting,
Intr EF reset time ) and the presence of
Protection functions
Intr
Intr EF
631