1MRS759142 F
Vector group of
the transformer
Zero-sequence component elimination
Clock number is "Clk Num 2", "Clk Num 4", "Clk Num 8" or "Clk Num 10", the vector
If
group matching is always done on both, winding 1 and winding 2. The combination
results in the correct compensation. In this case the zero-sequence component is
always removed from both sides automatically. The
cannot change this.
REX640
Technical Manual
Winding 1 type
ZNd4
ZN
Zd6
Z
ZNd6
ZN
Zd8
Z
ZNd8
ZN
Zd10
Z
ZNd10
ZN
Zz0
Z
ZNz0
ZN
ZNzn0
ZN
Zzn0
Z
Zz2
Z
ZNz2
ZN
ZNzn2
ZN
Zzn2
Z
Zz4
Z
ZNz4
ZN
ZNzn4
ZN
Zzn4
Z
Zz6
Z
ZNz6
ZN
ZNzn6
ZN
Zzn6
Z
Zz8
Z
ZNz8
ZN
ZNzn8
ZN
Zzn8
Z
Zz10
Z
ZNz10
ZN
ZNzn10
ZN
Zzn10
Z
Winding 2 type
Phase shift
d
d
d
d
d
d
d
z
z
zn
zn
z
z
zn
zn
z
z
zn
zn
z
z
zn
zn
z
z
zn
zn
z
z
zn
zn
Zro A elimination parameter
Protection functions
Zero sequence
current
elimination
4
(Automatic)
6
Not needed
6
HV side
8
Not needed
8
(Automatic)
10
Not needed
10
(Automatic)
0
Not needed
0
HV side
0
HV & LV side
0
LV side
2
Not needed
2
(Automatic)
2
(Automatic)
2
(Automatic)
4
Not needed
4
(Automatic)
4
(Automatic)
4
(Automatic)
6
Not needed
6
HV side
6
HV & LV side
6
LV side
8
Not needed
8
(Automatic)
8
(Automatic)
8
(Automatic)
10
Not needed
10
(Automatic)
10
(Automatic)
10
(Automatic)