ABB RELION REX640 Technical Manual page 196

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
RESTCTR Output signals
Table 124: RESTCTR Output signals
Name
ALARM
WARNING
IRES_MEAS
IRES_MEAS_DR
3.17.2.5
Settings
RESTCTR Settings
Table 125: RESTCTR Non group settings (Basic)
Parameter
Values (Range)
Current input type
2=Current trafo
4=Current sensor
Primary current
1.0...15000.0
Secondary current
1=0.2A
2=1A
3=5A
Rated secondary
1.000...150.000
Val
Amplitude Corr
0.9000...1.1000
Angle correction
-8.0000...8.0000
Table 126: RESTCTR Non group settings (Advanced)
Parameter
Values (Range)
Reverse polarity
0=False
1=True
Frequency adaptivi-
0=Disable
ty
1=Enable
3.17.2.6
Monitored data
Monitored data is available in three locations.
• Monitoring > I/O status > Analog inputs
• Monitoring > IED status > SMV traffic
• Monitoring > IED status > SMV accuracy
196
Type
BOOLEAN
BOOLEAN
SIGNAL
SIGNAL
Unit
Step
A
0.1
mV/Hz
0.001
0.0001
deg
0.0001
Unit
Step
1MRS759142 F
Description
Alarm
Warning
Residual current, measured
Residual current, measured,
for disturbance recorder
Default
Description
2=Current trafo
Type of the current
input
100.0
Primary current
2=1A
Secondary current
3.000
Rated Secondary
Value (RSV) ratio
1.0000
Amplitude correc-
tion
0.0000
Angle correction
factor
Default
Description
0=False
Reverse the polari-
ty of the residual
CT
0=Disable
Frequency adaptivi-
ty selection
Technical Manual
REX640

Advertisement

Table of Contents
loading