ABB RELION REX640 Technical Manual page 883

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
PSPTUV Input signals
Table 832: PSPTUV Input signals
Name
U3P
BLOCK
PSPTUV Output signals
Table 833: PSPTUV Output signals
Name
OPERATE
START
4.5.6.8
PSPTUV Settings
Table 834: PSPTUV Group settings (Basic)
Parameter
Values (Range)
Start value
0.010...1.200
Operate delay time
40...120000
Table 835: PSPTUV Group settings (Advanced)
Parameter
Values (Range)
Voltage block value 0.01...1.00
Enable block value
0=False
1=True
Table 836: PSPTUV Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 837: PSPTUV Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Relative hysteresis
1.0...5.0
REX640
Technical Manual
Type
SIGNAL
BOOLEAN
Type
BOOLEAN
BOOLEAN
Unit
Step
xUn
0.001
ms
10
Unit
Step
xUn
0.01
Unit
Step
Unit
Step
ms
1
%
0.1
Protection functions
Default
Description
-
Three-phase voltages
0=False
Block signal for acti-
vating the blocking
mode
Description
Operate
Start
Default
0.500
40
Default
0.20
1=True
Default
1=on
Default
20
4.0
Description
Start value
Operate delay time
Description
Internal blocking
level
Enable Internal
Blocking
Description
Operation Off / On
Description
Reset delay time
Relative hysteresis
for operation
883

Advertisement

Table of Contents
loading

Table of Contents