ABB RELION REX640 Technical Manual page 785

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
HIAPDIF Settings
Table 703: HIAPDIF Group settings (Basic)
Parameter
Values (Range)
Operate value
1.0...200.0
Minimum operate
20...300000
time
Table 704: HIAPDIF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 705: HIAPDIF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
HIBPDIF Settings
Table 706: HIBPDIF Group settings (Basic)
Parameter
Values (Range)
Operate value
1.0...200.0
Minimum operate
20...300000
time
Table 707: HIBPDIF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 708: HIBPDIF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
HICPDIF Settings
Table 709: HICPDIF Group settings (Basic)
Parameter
Values (Range)
Operate value
1.0...200.0
Minimum operate
20...300000
time
Table 710: HICPDIF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
REX640
Technical Manual
Unit
Step
%In
1.0
ms
10
Unit
Step
Unit
Step
ms
10
Unit
Step
%In
1.0
ms
10
Unit
Step
Unit
Step
ms
10
Unit
Step
%In
1.0
ms
10
Unit
Step
Protection functions
Default
Description
5.0
Operate value, per-
centage of the
nominal current
20
Minimum operate
time
Default
Description
1=on
Operation Off / On
Default
Description
20
Reset delay time
Default
Description
5.0
Operate value, per-
centage of the
nominal current
20
Minimum operate
time
Default
Description
1=on
Operation Off / On
Default
Description
20
Reset delay time
Default
Description
5.0
Operate value, per-
centage of the
nominal current
20
Minimum operate
time
Default
Description
1=on
Operation Off / On
785