Station Authority Level "L,S,S+R,L+S,L+S+R - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
Table 76: Station authority level "L,S,R" using CONTROL function block
L/R Control
R/L button
CTRL.LLN0.LocS
4
ta
CTRL_OFF
FALSE
CTRL_LOC
FALSE
CTRL_STA
TRUE
7
CTRL_REM
TRUE
CTRL_REM
FALSE
CTRL_ALL
FALSE
3.8.7

Station authority level "L,S,S+R,L+S,L+S+R"

Station authority level "L,S,S+R,L+S,L+S+R" adds station control access together
with several different multilevel access scenarios. Control access can also be
simultaneously permitted from local, station or remote location. Simultaneous local,
station or remote control operation is not allowed as one client and location at time
can access controllable objects and they remain reserved until the previously started
control operation is first completed by the client.
IEC 61850
station
Figure 54: Station authority is "L,S,S+R,L+S,L+S+R"
When station authority level "L,S,S+R,L+S,L+S+R" is used, control access can be
selected using R/L button or CONTROL function block. IEC 61850 data object
CTRL.LLN0.LocSta and CONTROL function block input CTRL_STA are applicable for
this station authority level.
"Station" and "Local + Station" control access can be reserved by using R/L
button or CONTROL function block in combination with IEC 61850 data object
CTRL.LLN0.LocSta.
4
Station client reserves the control operating by writing controllable point LocSta.
5
Client IEC 61850 command originator category is remote.
6
Client IEC 61850 command originator category is station.
7
CTRL_STA unconnected in application configuration. Station client reserves the control operating
by writing controllable point LocSta.
140
L/R Control status
CTRL.LLN0.MltL
ev
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
LOCAL
STATION
IEC 61850
IEC 61850
remote
remote
IEC 61850
station
IED
IED
Control access
L/R state
Local user
CTRL.LLN0.Loc
KeyHMI
0
1
3
3
2
0
S+R
L+S
IEC 61850
IEC 61850
remote
remote
IEC 61850
IEC 61850
station
station
IED
IED
IEC 61850 client
5
x
x
L+S+R
OFF
IEC 61850
IEC 61850
remote
remote
IEC 61850
IEC 61850
station
station
IED
IED
Technical Manual
1MRS759142 F
IEC 61850
6
client
x
REX640