ABB RELION REX640 Technical Manual page 128

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
Time settings
Table 57: Non group settings
Parameter
Values (Range)
Synch source
0=None
1=SNTP
2=Modbus
3=IEEE 1588
5=IRIG-B
9=DNP
17=IEC60870-5-103
PTP Profile
1=IEEE
C37.238-2011
2=IEC 61850-9-3
PTP domain ID
0...255
PTP priority 1
0...255
PTP priority 2
0...255
PTP Slave-only
0=False
1=True
Time master mode
1=Master with fi-
nite holdover
2=Master with in-
finite holdover
Clear clock list
0=False
1=True
Time Syn Src Tmm
1...65535
Table 58: Non group settings
Parameter
Values (Range)
Date
Time
Local time offset
-840...840
Table 59: Non group settings
Parameter
Values (Range)
IP SNTP primary
IP SNTP secondary
128
Unit
Step
1
1
1
min
1
Unit
Step
min
1
Unit
Step
1MRS759142 F
Default
Description
1=SNTP
Time synchroniza-
tion source
1=IEEE
Profile Selection for
C37.238-2011
the Precision Time
Protocol
0
The domain is iden-
tified by an inte-
ger, the domain-
Number, in the
range of 0 to 255.
128
PTP priority 1, in
the range of 0 to
255.
128
PTP priority 2, in
the range of 0 to
255.
0=False
If true, the IED can-
not become a clock
master
1=Master with fi-
Device Time Master
nite holdover
Mode
0=False
Clears the stored
master clock list
3
Time synchroniza-
tion timeout for
legacy protocols as
clock source (Mod-
bus, IEC103, IEC101,
IEC104 and DNP)
Default
Description
0
Date
0
Time
0
Local time offset in
minutes
Default
Description
192.168.2.166
IP address for SNTP
primary server
192.168.2.165
IP address for SNTP
secondary server
Technical Manual
REX640

Advertisement

Table of Contents
loading

Table of Contents