ABB RELION REX640 Technical Manual page 604

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Figure 343: Operation timer characteristic of IFPTOC function when Operation
principle = "EF-current based" and Operating curve type = "Inverse time EN50522".
Setting UTp multiplier is 1.0, Maximum earthing Ris = 10ohms, EF current Str Val =
0.02*In (2A), IDMT stage Min Op Tm = 100 ms and IDMT stage Max Op Tm = 5000
ms. Reduction factor = 1.0. Characteristics are according to standard EN50522.
Example 2b. Inverse time operation of IFPTOC, when
current based" and
Figure 344
minimum operate time 100 ms and maximum operate time of 5000 ms. Setting
multiplier is 2.0 and setting Maximum earthing Ris is 10 ohms. Reduction factor =
1.0. For illustrating the operating speed requirement of protection, limits of earth
potential rise durations defined in standard EN50522 scaled into corresponding
earth-fault current requirements using the maximum earthing resistance R
(setting
reference.
604
Operating curve type = "Inverse time EN50522" is illustrated in
. Start value for operation is set to be 0.04*In (4 A). IFPTOC is set to have
Maximum earthing Ris ) encountered in protected feeder are shown for
1MRS759142 F
Operation principle = "EF-
Technical Manual
UTp
Emax
REX640

Advertisement

Table of Contents
loading

Table of Contents