1MRK 514 030-UEN B
they should not be run in the same cable ducts or loom. The connections are made on
connector X11.
6.1.4

Connecting the binary input and output signals

Auxiliary power and signals are connected using voltage connectors. Signal wires are
connected to a female connector (see Figure 13) which is then plugged into the corresponding
male connector (see Figure 14) located at the rear of the IED. For location of BIM, BOM, SOM
and IOM refer to section
IOM are shown in Figure 6, Figure 9, Figure
If the IED is equipped with a test-switch of type RTXP 24, COMBIFLEX wires with 20 A sockets,
1.5mm² (AWG16) conductor area must be used to connect the auxiliary power.
Procedure
1.
Connect signals to the female connector
The conductors can be of rigid type (solid, stranded) or of flexible type.
The female connectors accept conductors with a cross section area of 0.2-2.5 mm
24-14). If two conductors are used in the same terminal, the maximum permissible cross
section area is 0.2-1 mm
If two conductors, each with area 1.5 mm
terminal, a ferrule must be used, see figure 15. Crimp this ferrule properly to the wire
using tools as recommended by the supplier of the ferrules (keep stripping length of the
cable to minimum 10 mm). The fastening screw shall be tightened with a torque of 0.4
Nm (This torque applies to all binary connectors).
2.
Plug the female connector to the corresponding back-side mounted male connector
3.
Lock the female connector by fastening the lock screws
Switchgear control unit SAM600-IO
Installation manual
"Rear side
connectors". Connection diagrams for BIM, BOM, SOM and
Do not insert anything else to the female connector but the corresponding
male connector. Inserting anything else (such as a measurement probe) may
violate the female connector and prevent a proper electrical contact between
the printed circuit board and the external wiring connected to the screw
terminal block.
2
(AWG 24-18).
© Copyright 2017 ABB. All rights reserved
10
and Figure 11.
2
(AWG 16) need to be connected to the same
Section 6
Connecting
M11992-9 v8
2
(AWG
29