ABB RELION REX640 Technical Manual page 113

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
-F1
Figure 34: Motor feeder fail-safe trip circuit principle, example 4
J01
J02
ES
Q0
TO1
TO2
IRF
BI1
<U
TC1
F1
In example 4, the fail-safe approach aims at securing motor shutdown via an
emergency switch and in case the control voltage disappears. The adjacent panels
provide backup for each other in internal relay fault situations. In case of an internal
relay fault, the situation is noticed by the relay in the adjacent panel and the circuit
breaker in the panel with the faulty relay is tripped after a preset time delay. The
additional time delay allows the relay to recover from the internal fault situation
without tripping the circuit breaker.
3.3.4.2
Other critical feeders
The examples given for motor feeders can be applied for other types of feeders as
well. The following examples are for critical feeders in which the protection system
dependability, security or both are the drivers.
REX640
Technical Manual
Control +
+J01
+J02 -A1
+J02 -A1
-A1
ES
TO2
TO1
-Q0
<U
TC1
Control -
Feeder #1 panel
Feeder #2 panel
Emergency stop
Circuit breaker
Relay trip output #1
Relay trip output #2
Relay internal fault indication
Relay binary input #1
CB undervoltage trip coil
CB trip coil 1
Miniature circuit breaker
-F1
Control +
IRF
ES
BI1
-Q0
<U
Control -
Basic functions
+J02
+J01 -A1
IRF
+J01 -A1
-A1
TO2
TO1
BI1
TC1
113