ABB RELION REX640 Technical Manual page 238

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
3.20.3.2
Function block
Figure 128: Function block
3.20.3.3
Functionality
The daily timer function DTMGAPC is used to activate or deactivate its output at the
set time of the day. It is possible to set a different activation or deactivation time
separately for each day of the week.
3.20.3.4
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "on" and "off".
The operation of DTMGAPC can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
Figure 129: Functional module diagram
Time comparator
This module compares the current day and time with the activation hour and minute
defined with the settings
of the day reaches the set activation time, output Q is activated and remains active
for the duration defined by the setting
Different activation and deactivation times can be set for all days of the week. The
activation and deactivation can also be disabled for a specific day. For example, if
the activation or deactivation is not needed on Sundays, the setting
enable can be set as "False".
Activation of the BLOCK input deactivates the function output whereas the
activation of the FREEZE input freezes the output. The BLOCK input always has a
higher priority than the FREEZE input.
3.20.3.5
Application
DTMGAPC is useful in applications that require signal activation and deactivation
at a specific time of the day. Different activation times and duration can be set for
238
BLOCK
comparator
FREEZE
The output remains active until the next day if the value for
is set so that it results into rollover of the day.
Time
Q
xxx Act hour and xxx Act Mn , respectively. When the time
xxx off delay .
1MRS759142 F
Operation setting. The
xxx off delay
Sunday Act
Technical Manual
REX640