ABB RELION REX640 Technical Manual page 585

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
document. The configuration can be written to the protection relay once the
mismatch is corrected.
4.2.10.5
Operation principle
The
the function is enabled and respectively "off" means function is disabled.
The operation of
described by using a module diagram (see figure below). All the modules in the
diagram are explained in the next sections.
Uo
URES
U_A
U3P
U_B
U_C
U_AB
U_BC
U_CA
Io
IRES
I_A
I3P
I_B
I_C
EXT_RELEASE
BLOCK
CB_CL_CMD
TRIGG_REC
Figure 335: Functional module diagram
General fault criterion
The General fault criterion (GFC) module monitors the presence of earth fault in the
network. It is based on the value of the fundamental frequency residual voltage
REX640
Technical Manual
Operation setting is used to enable or disable the function. When selected "on"
Touch voltage-based earth-fault current protection IFPTOC can be
General
fault
Fault
criterion
current
estimation
validity
check
Fault
resistance
estimation
Faulted
phase
identifi-
cation
Blocking
logic
and
Touch
voltage
estimation
Protection functions
Trip logic
Earth-fault
current &
touch
voltage
protection
Cross-
country
fault
protection
Intermittent
earth fault
protection
Switch
onto fault
protection
Recorded
data
EF_IND
VALID_EF
OPERATE
START
OP_EF
ST_EF
OP_XC
ST_XC
XC_FLT
OP_INTR
ST_INTR
PEAK_IND
INTR_EF
OP_SOTF
ST_SOTF
585