ABB RELION REX640 Technical Manual page 340

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Parameter
Values (Range)
Time multiplier
0.025...15.000
Operate delay time
40...300000
Operating curve
1=ANSI Ext. inv.
type
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
20=UK rectifier
Table 374: PHLPTOC Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Table 375: PHLPTOC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Num of start pha-
1=1 out of 3
ses
2=2 out of 3
3=3 out of 3
Curve parameter A
0.0086...50000.000
0
Curve parameter B
0.0000...0.7120
Curve parameter C
0.02...6.00
Curve parameter D
0.46...30.00
Curve parameter E
0.0...1.0
340
Unit
Step
0.005
ms
10
Unit
Step
Unit
Step
0.0001
0.0001
0.01
0.01
0.1
1MRS759142 F
Default
Description
1.000
Time multiplier
in IEC/ANSI IDMT
curves
40
Operate delay time
15=IEC Def. Time
Selection of time
delay curve type
Default
Description
1=Immediate
Selection of reset
curve type
Default
Description
1=on
Operation Off / On
1=1 out of 3
Number of phases
required for oper-
ate activation
28.2000
Parameter A for
customer program-
mable curve
0.1217
Parameter B for
customer program-
mable curve
2.00
Parameter C for
customer program-
mable curve
29.10
Parameter D for
customer program-
mable curve
1.0
Parameter E for
customer program-
mable curve
Technical Manual
REX640

Advertisement

Table of Contents
loading