ABB RELION REX640 Technical Manual page 931

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
The df/dt detection module includes a timer with the DT characteristics. Upon
detection of df/dt, operation timer activates the ST_FRG output. When the timer
has reached the value set by
if the df/dt condition still persists. If df/dt becomes normal before the module
operates, the reset timer is activated. If the reset timer reaches the value of the
Reset delay time setting, the timer resets and the ST_FRG output is deactivated.
Load-shedding control
The way of load-shedding, that is, whether to operate based on underfrequency
or high df/dt or both, is defined with the
operation modes for the
and "Freq< OR df/dt".
Once the selected operation mode conditions are satisfied, the START and OPERATE
output signals are activated.
When the START output is active, the percentage of the elapsed delay time can be
monitored through START_DUR which is available as monitored data.
REX640
Technical Manual
Operate Tm df/dt , the OPR_FRG output is activated
Load shed mode user setting. The valid
Load shed mode settings are "Freq<", "Freq< AND df/dt"
Protection functions
931