ABB RELION REX640 Technical Manual page 789

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.3.7.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of MPDIF can be described using a module diagram. All the modules
in the diagram are explained in the next sections.
BLK_OPR_LS
BLK_OPR_HS
Figure 449: Functional module diagram
Differential and bias calculation
Differential calculation module calculates the differential current. The differential
current is the difference in current between the phase and neutral sides of the
machine.
The phase currents I
the phase and neutral sides of the current. The amplitude of the differential current I
is obtained using the equation (assuming that the positive direction of the current
d
is towards the machine):
REX640
Technical Manual
I_A1
I_B1
I3P1
I_C1
I_A2
I_B2
I3P2
I_C2
BLOCK
and I
1
Differential
and bias
calculation
Through
fault
detection
DC restraint
CT
saturation
based
blocking
denote the fundamental frequency components on
2
Protection functions
Operation setting. The
Instan-
OPERATE
taneous
high stage
OPR_LS
OPR_HS
Biased low
stage
INT_BLKD
789