1MRS759142 F
Forward directional overconductance characteristic
The forward directional overconductance criterion is enabled with the
mode setting set to "Go" and Directional mode set to "Forward". The characteristic
is defined by one overconductance boundary line with the
setting. For the sake of application flexibility, the boundary line can be tilted with
the angle defined with the
zero degrees, that is, the boundary line is a vertical line in the admittance plane. A
positive tilt value rotates the boundary line counterclockwise from the vertical axis.
Operation is achieved when the measured admittance moves over the boundary
line.
Figure 287: Forward directional overconductance characteristic. Left figure: classical
forward directional overconductance criterion. Middle figure: characteristic is tilted
with negative tilt angle. Right figure: characteristic is tilted with positive tilt angle.
Forward directional oversusceptance characteristic
The forward directional oversusceptance criterion is enabled with the
mode setting set to "Bo" and Directional mode to "Forward". The characteristic
is defined by one oversusceptance boundary line with the
setting. For the sake of application flexibility, the boundary line can be tilted by the
angle defined with the
degrees, that is, the boundary line is a horizontal line in the admittance plane. A
positive tilt value rotates the boundary line counterclockwise from the horizontal
axis.
Operation is achieved when the measured admittance moves over the boundary
line.
REX640
Technical Manual
Conductance tilt Ang setting. By default, the tilt angle is
The forward directional overconductance criterion is applicable in high-
resistance earthed and compensated networks. It must not be applied in
unearthed networks.
Susceptance tilt Ang setting. By default, the tilt angle is zero
The forward directional oversusceptance criterion is applicable in
unearthed networks. It must not be applied to compensated networks.
Protection functions
Operation
Conductance forward
Operation
Susceptance forward