Protection functions
Table 433: Analog inputs
Input
I3P
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.1.5.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of T1PTTR can be described using a module diagram. All the modules
in the diagram are explained in the next sections.
The function uses ambient temperature which can be measured locally or remotely.
Local measurement is done by the protection relay. Remote measurement uses
analog GOOSE to connect AMB_TEMP input.
ENA_MULT
AMB_TEMP
BLK_OPR
Figure 227: Functional module diagram
Max current selector
The max current selector of the function continuously checks the highest measured
TRMS phase current value. The selector reports the highest value to the temperature
estimator.
Temperature estimator
The final temperature rise is calculated from the highest of the three-phase currents
according to the expression:
384
See the preprocessing function blocks in this document for the possible
signal sources.
If the quality of remotely measured temperature is invalid or
communication channel fails the function uses ambient temperature set
Env temperature Set .
in
I_A
I_B
I3P
I_C
Description
Three-phase currents
Max current
Temperature
selector
estimator
1MRS759142 F
Operation setting. The
OPERATE
Thermal
counter
BLK_CLOSE
Technical Manual
START
ALARM
REX640