Protection functions
operates, the reset timer is activated. If the reset timer reaches the value set by
Reset delay time , the operate timer resets and the START output is deactivated.
The timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operating time. The value is
available through the monitored data view.
The BLOCK signal blocks the operation of the function and resets the timer.
4.1.9.6
Application
In some cases, smaller distribution power transformers are used where the high-
side protection involves only power fuses. When one of the high-side fuses blows
in a single-phase condition, knowledge of it on the secondary side is lacking. The
resulting negative-sequence current leads to a premature failure due to excessive
heating and breakdown of the transformer insulation. Knowledge of this condition
when it occurs allows for a quick fuse replacement and saves the asset.
The
three-phase current. However, this results in an unnecessary event sending when
the transformer or protected object is disconnected.
Phase-specific start and operate can give a better picture about the evolving faults
when one phase has started first and another follows.
PHPTUC is meant to be a general protection function, so that it could be used in
other cases too.
In case of undercurrent-based motor protection, see the Loss of load protection.
4.1.9.7
Signals
Table 468: PHPTUC Input signals
Name
I3P
BLOCK
Table 469: PHPTUC Output signals
Name
OPERATE
OPR_A
OPR_B
OPR_C
START
ST_A
ST_B
ST_C
408
Current block value setting can be set to zero to not block PHPTUC with a low
Type
SIGNAL
BOOLEAN
Default
0=False
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1MRS759142 F
Description
Three-phase currents
Block all binary outputs by resetting
timers
Description
Operate
Operate phase A
Operate phase B
Operate phase C
Start
Start phase A
Start phase B
Start phase C
Technical Manual