ABB RELION REX640 Technical Manual page 363

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Parameter
Values (Range)
Operate delay time
40...300000
Operating curve
1=ANSI Ext. inv.
type
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Directional mode
1=Non-directional
2=Forward
3=Reverse
Characteristic an-
-179...180
gle
Max forward angle
0...90
Max reverse angle
0...90
Min forward angle
0...90
Min reverse angle
0...90
Table 403: DPHLPDOC Group settings (Advanced)
Parameter
Values (Range)
Type of reset curve
1=Immediate
2=Def time reset
3=Inverse reset
Voltage Mem time
0...3000
Pol quantity
1=Self pol
4=Neg. seq. volt.
5=Cross pol
7=Pos. seq. volt.
REX640
Technical Manual
Unit
Step
ms
10
deg
1
deg
1
deg
1
deg
1
deg
1
Unit
Step
ms
1
Protection functions
Default
Description
40
Operate delay time
15=IEC Def. Time
Selection of time
delay curve type
2=Forward
Directional mode
60
Characteristic an-
gle
80
Maximum phase
angle in forward di-
rection
80
Maximum phase
angle in reverse di-
rection
80
Minimum phase an-
gle in forward di-
rection
80
Minimum phase an-
gle in reverse direc-
tion
Default
Description
1=Immediate
Selection of reset
curve type
40
Voltage memory
time
5=Cross pol
Reference quantity
used to determine
fault direction
363

Advertisement

Table of Contents
loading

Table of Contents