Protection functions
4.2.10.6
Signals
IFPTOC Input signals
Table 637: IFPTOC Input signals
Name
I3P
IRES
U3P
URES
EXT_RELEASE
BLOCK
CB_CL_CMD
TRIGG_REC
IFPTOC Output signals
Table 638: IFPTOC Output signals
Name
OPERATE
START
ST_EF
ST_XC
ST_SOTF
ST_INTR_EF
OP_EF
Table continues on the next page
638
Type
Default
SIGNAL
-
SIGNAL
-
SIGNAL
-
SIGNAL
-
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
1MRS759142 F
Description
Three-phase currents
Residual current
Three-phase voltages
Residual voltage
External GFC start
signal, alternative for
internal GFC module.
Block signal for acti-
vating the blocking
mode
Defines breaker close
command. This signal
is used in the switch
on to fault (SOTF)
logic.
External recorded da-
ta triggering. There
are two recorded data
banks available.
Description
Operate
Start
Start signal according to
estimated fault current or
touch voltage according to
the standards
Start signal according to
cross-country stage earth-
fault module
Start signal according to
SOTF-module
Start signal according to in-
termittent earth-fault module
Operate signal according to
estimated fault current or
REX640