Protection functions
MHZPDIF Output signals
Table 728: MHZPDIF Output signals
Name
OPERATE
START
4.3.8.10
MHZPDIF Settings
Table 729: MHZPDIF Group settings (Basic)
Parameter
Values (Range)
Operate value
0.5...50.0
Minimum operate
20...300000
time
Table 730: MHZPDIF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 731: MHZPDIF Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
4.3.8.11
MHZPDIF Monitored data
Table 732: MHZPDIF Monitored data
Name
Type
START_DUR
FLOAT32
ID_A
FLOAT32
ID_B
FLOAT32
ID_C
FLOAT32
MHZPDIF
Enum
818
Type
BOOLEAN
BOOLEAN
Unit
Step
%In
0.1
ms
10
Unit
Step
Unit
Step
ms
1
Values (Range)
0.00...100.00
0.00...80.00
0.00...80.00
0.00...80.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Description
Operate
Start
Default
0.5
20
Default
1=on
Default
0
Unit
Description
%
Ratio of start time / op-
erate time
xIn
Differential current
phase A
xIn
Differential current
phase B
xIn
Differential current
phase C
Status
1MRS759142 F
Description
Operate value, per-
centage of the
nominal current
Minimum operate
time
Description
Operation Off / On
Description
Reset delay time
REX640
Technical Manual