1MRS759142 F
Unit selection set to Count
Pulse quantity set to 10
Figure 150: Behavior of FREEZE_COUNT input
3.20.14.5
Application
PCGAPC counts externally generated binary pulses, for example, pulses coming
from an external energy meter, for the calculation of energy consumption values.
The pulses are captured by the binary input module and read by PCGAPC with a
frequency of up to 40 Hz. The number of pulses in the counter is then reported
via the station bus to the substation automation system or read via the station
monitoring system as a service value. When using IEC 61850, a scaled service value
is available over the station bus.
REX640
Technical Manual
PULSE_INPUT
Reporting time
1
Internal counter
COUNT_VALUE
FREEZE_COUNT
READ_VALUE
VALUE_READ
SCALED_VALUE
Reporting time
5
4
3
2
5
3
50
30
Basic functions
Reporting time
Reporting time
7
6
6
Fixed pulse of 200ms
60
9
8
9
90
269