1MRS759142 F
RPTTR Output signals
Table 489: RPTTR Output signals
Name
OPERATE
ALARM
BLK_RESTART
STALL_IND
TEMP_RL
4.1.11.8
RPTTR Settings
Table 490: RPTTR Group settings (Basic)
Parameter
Values (Range)
Env temperature
1=FLC Only
mode
2=Use input
3=Set Amb Temp
Env temperature
-20.0...70.0
Set
Overload factor
1.00...1.20
Alarm value
50.0...100.0
Restart thermal Val 20.0...80.0
Weighting factor p
20.0...100.0
Time constant nor-
80...10000
mal
Time constant start 80...10000
Time constant stop 80...60000
Table 491: RPTTR Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Relative starting
0.10...3.00
torque
Table continues on the next page
REX640
Technical Manual
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
FLOAT32
Unit
Step
°C
0.1
0.01
%
0.1
%
0.1
%
0.1
s
1
s
1
s
1
Unit
Step
0.01
Protection functions
Description
Operate
Thermal Alarm
Thermal overload indicator,
to inhibit restart
Indicates that the rotor is
stalling
The calculated temperature
of the protected object rela-
tive to the operate level
Default
Description
1=FLC Only
Mode of measur-
ing ambient tem-
perature
40.0
Ambient tempera-
ture used when
no external temper-
ature measurement
available
1.05
Overload factor (k)
95.0
Temperature level
for start (alarm)
40.0
Thermal level above
which function in-
hibits motor re-
starting
50.0
Weighting factor
(p)
320
Rotor time con-
stant during the
normal operation
of motor
320
Rotor time con-
stant during the
start of motor
500
Rotor time con-
stant during the
standstill condition
of motor
Default
Description
1=on
Operation Off / On
0.70
Relative starting
torque i.e. locked
rotor torque
433