ABB RELION REX640 Technical Manual page 826

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
4.4.2.2
Function block
Figure 467: Function block
4.4.2.3
Functionality
The directional negative-sequence overcurrent protection function DNSPDOC is
used as directional overcurrent and short-circuit protection.
DNSPDOC starts up when the fundamental value of the operating quantity
(negative-sequence or residual current) exceeds the set limit and the directional
criterion is fulfilled. The operate time characteristic is according to definite time
(DT).
The function contains a blocking functionality. It is possible to block function
outputs, timers or the function itself.
4.4.2.4
Analog channel configuration
DNSPDOC has three analog group inputs which must be properly configured.
Table 743: Analog inputs
Input
I3P
IRES
U3P
There are a few special conditions which must be noted with the configuration.
Table 744: Special conditions
Condition
U3P connected real measurements
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
3
Can be connected to GRPOFF if
826
3
See the preprocessing function blocks in this document for the possible
signal sources. The GRPOFF signal is available in the function block called
Protection.
Operating quantity is set to "Negative seq"
Description
Three-phase currents
Residual current (measured or calculated)
Necessary when
Operating quantity is "Re-
sidual" or "Residual (calc)"
Three-phase voltages
Description
The function requires that at least two volt-
age channels are connected.
1MRS759142 F
REX640
Technical Manual