Protection functions
Operation mode
Freq< OR df/dt
Freq> OR df/dt
The module calculates the start duration value which indicates the percentage ratio
of the start situation and set operate time (DT). The start duration is available
according to the selected value of the
Table 882: Start duration value
Operation mode in use
Freq<
Freq>
df/dt
The combined start duration START_DUR indicates the maximum percentage ratio
of the active protection modes. The values are available via the Monitored data view.
924
Description
A parallel operation between the protection methods is en-
abled. The
output is activated when either of the
START
measured values of the protection module exceeds its set
value. Detailed information about the active module is availa-
ble at the
and
STR_UFRQ
operate delay time from the set
ate Tm df/dt is dominant regarding the
The time characteristic is according to DT. The characteristic
that activates the
OPERATE
or
OPR_UFRQ
OPR_FRG
restores before the module operates, the reset timer is acti-
vated. If the timer reaches the value set by the
Tm df/dt setting, the operate timer resets and the
output is deactivated. If the frequency restores before the
module operates, the reset timer is activated. If the timer
reaches the value set by the
operate timer resets and the
ted.
A parallel operation between the protection methods is en-
abled. The
output is activated when either of the
START
measured values of the protection module exceeds its set
value. A detailed information from the active module is avail-
able at the
and
STR_OFRQ
operate delay time from the set
ate Tm df/dt is dominant regarding the
The time characteristic is according to DT. The characteristic
that activates the
OPERATE
or
OPR_OFRQ
OPR_FRG
restores before the module operates, the reset timer is acti-
vated. If the timer reaches the value set by the
Tm df/dt setting, the operate timer resets and the
output is deactivated. If the frequency restores before the
module operates, the reset timer is activated. If the timer
reaches the value set by the
operate timer resets and the
ted.
Operation mode setting.
Available start duration value
ST_DUR_UFRQ
ST_DUR_OFRQ
ST_DUR_FRG
1MRS759142 F
outputs. The shortest
STR_FRG
Operate Tm Freq or Oper-
OPERATE
output can be seen from the
output. If the frequency gradient
Reset delay
Reset delay Tm Freq setting, the
output is deactiva-
STR_UFRQ
outputs. The shortest
STR_FRG
Operate Tm Freq or Oper-
OPERATE
output can be seen from the
output. If the frequency gradient
Reset delay
Reset delay Tm Freq setting, the
output is deactiva-
STR_UFRQ
Technical Manual
output.
STR_FRG
output.
STR_FRG
REX640