ABB RELION REX640 Technical Manual page 105

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Fault
Fault indication
code
Internal Fault
-25
PO-relay(s), Slot
F
Internal Fault
-26
PO-relay(s), Slot
G
Internal Fault
-27
PO-relay(s), Slot
A1
Internal Fault
-30
Conf. error, Slot
C
Internal Fault
-31
Conf. error, Slot
E
Internal Fault
-32
Conf. error, Slot
A2
Internal Fault
-33
Conf. error, Slot
B
Internal Fault
-34
Conf. error, Slot
D
Table continues on the next page
REX640
Technical Manual
Fast self-
Additional
recovery
information
attempt
Runtime error:
Yes
Faulty Power Out-
put relay(s) in card
located in slot F.
Runtime error:
Yes
Faulty Power Out-
put relay(s) in card
located in slot G.
Runtime error:
Yes
Faulty Power Out-
put relay(s) in card
located in slot A1.
Start up error: Card
No
in slot C is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
Start up error: Card
No
in slot E is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
Start up error: Card
No
in slot A2 is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
Start up error: Card
No
in slot B is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
Start up error: Card
No
in slot D is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
Slow 10min
self-
recovery
Immediate
(# of
attempts)
IRF-mode
Yes (3)
No
Yes (3)
No
Yes (3)
No
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
Basic functions
Action in permanent fault
state
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot F.
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot G.
Check wirings. Restart the
relay. If recovered by re-
starting, continue relay nor-
mal operation. If not recov-
er by restarting, exchange
the hardware module in
slot A1.
Check that the card in slot
C is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot C.
Check that the card in slot
E is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot E.
Check that the communica-
tion card in slot A2 is prop-
er type and properly instal-
led. Then restart the relay.
If does not then recover by
restarting, it is hardware
module failure most likely
in question. Exchange the
communication module in
slot A2.
Check that the card in slot
B is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot B.
Check that the card in slot
D is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
105