ABB RELION REX640 Technical Manual page 388

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
T1PTTR Output signals
Table 435: T1PTTR Output signals
Name
OPERATE
START
ALARM
BLK_CLOSE
4.1.5.8
T1PTTR Settings
Table 436: T1PTTR Group settings (Basic)
Parameter
Values (Range)
Env temperature
-50...100
Set
Current reference
0.05...4.00
Temperature rise
0.0...200.0
Time constant
60...60000
Maximum tempera-
22.0...200.0
ture
Alarm value
20.0...150.0
Reclose tempera-
20.0...150.0
ture
Table 437: T1PTTR Group settings (Advanced)
Parameter
Values (Range)
Current multiplier
1...5
Table 438: T1PTTR Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 439: T1PTTR Non group settings (Advanced)
Parameter
Values (Range)
Initial temperature
-50.0...100.0
388
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
°C
1
xIn
0.01
°C
0.1
s
1
°C
0.1
°C
0.1
°C
0.1
Unit
Step
1
Unit
Step
Unit
Step
°C
0.1
1MRS759142 F
Description
Operate
Start
Thermal Alarm
Thermal overload indicator.
To inhibite reclose.
Default
Description
40
Ambient tempera-
ture used when
no external temper-
ature measurement
available
1.00
The load current
leading to Temper-
ature raise temper-
ature
75.0
End temperature
rise above ambient
2700
Time constant of
the line in seconds.
90.0
Temperature level
for operate
80.0
Temperature level
for start (alarm)
70.0
Temperature for re-
set of block reclose
after operate
Default
Description
1
Current multiplier
when function is
used for parallel
lines
Default
Description
1=on
Operation Off / On
Default
Description
0.0
Temperature raise
above ambient
temperature at
startup
Technical Manual