ABB RELION REX640 Technical Manual page 912

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Vector shift and rate of change of frequency are two parallel criteria typically used
for detection of Loss of Mains.
Chosen protection criteria can be included in the Application Configuration tool to
create multicriteria loss of mains alarm or trip.
4.5.9.7
Signals
VVSPPAM Input signals
Table 862: VVSPPAM Input signals
Name
U3P
BLOCK
VVSPPAM Output signals
Table 863: VVSPPAM Output signals
Name
OPERATE
INT_BLKD
4.5.9.8
VVSPPAM Settings
Table 864: VVSPPAM Group settings (Basic)
Parameter
Values (Range)
Start value
2.0...30.0
Table 865: VVSPPAM Group settings (Advanced)
Parameter
Values (Range)
Over Volt Blk value
0.40...1.50
Under Volt Blk value 0.15...1.00
Table 866: VVSPPAM Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
912
Type
SIGNAL
BOOLEAN
Type
BOOLEAN
BOOLEAN
Unit
Step
deg
0.1
Unit
Step
xUn
0.01
xUn
0.01
Unit
Step
Default
Description
-
Three-phase voltages
0=False
Block signal for acti-
vating the blocking
mode
Description
Operate
Protection function internally
blocked
Default
6.0
Default
1.20
0.80
Default
1=on
1MRS759142 F
Description
Start value for vec-
tor shift
Description
Voltage above
which function
will be internally
blocked
Voltage below
which function
will be internally
blocked
Description
Operation Off / On
REX640
Technical Manual