1MRS759142 F
4.5.10.8
PHVPTOV Settings
Table 874: PHVPTOV Group settings (Basic)
Parameter
Values (Range)
Start value
0.05...3.00
Time interval
1...120
Operate delay Mult
0...100
Table 875: PHVPTOV Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Num of start pha-
1=1 out of 3
ses
2=2 out of 3
3=3 out of 3
Voltage selection
1=phase-to-earth
2=phase-to-phase
Table 876: PHVPTOV Non group settings (Advanced)
Parameter
Values (Range)
Relative hysteresis
1.0...5.0
4.5.10.9
PHVPTOV Monitored data
Table 877: PHVPTOV Monitored data
Name
Type
START_DUR
FLOAT32
U_MEAN_A
FLOAT32
U_MEAN_B
FLOAT32
U_MEAN_C
FLOAT32
U_MEAN_AB
FLOAT32
U_MEAN_BC
FLOAT32
U_MEAN_CA
FLOAT32
PHVPTOV
Enum
REX640
Technical Manual
Unit
Step
xUn
0.01
min
1
1
Unit
Step
Unit
Step
%
0.1
Values (Range)
0.00...100.00
0.00...5.00
0.00...5.00
0.00...5.00
0.00...5.00
0.00...5.00
0.00...5.00
1=on
2=blocked
3=test
4=test/blocked
5=off
Protection functions
Default
1.10
10
1
Default
1=on
1=1 out of 3
1=phase-to-earth
Default
4.0
Unit
Description
%
Ratio of start time / op-
erate time
xUn
Mean value of phase to
earth voltage A
xUn
Mean value of phase to
earth voltage B
xUn
Mean value of phase to
earth voltage C
xUn
Mean value of Phase to
phase voltage AB
xUn
Mean value of Phase to
phase voltage BC
xUn
Mean value of Phase to
phase voltage CA
Status
Description
Start value
Time interval for
average voltage
calculation
Trip delay ex-
pressed as a multi-
ple of refresh time
Description
Operation Off / On
Number of phases
required for oper-
ate activation
Parameter to select
phase or phase-to-
phase voltages
Description
Relative hysteresis
for operation
919