The module calculates the start duration value
percentage ratio of the start time and the set operating time. The value is available
in the monitored data view.
Timer 2
Once activated, the alarm timer is activated. The time characteristics are according
to DT. When the alarm timer reaches the value set by
output is activated. If the fault disappears before the module generates an ALARM
signal, the reset timer is activated. If the reset timer reaches the value set by
delay time , the alarm timer resets. The activation of the BLOCK signal resets the
Timer 2 and deactivates the ALARM output.
4.1.12.6
Application
In order to prevent the generator shaft from getting electrically charged the
shaft is grounded. Different types of generators have different ways for shaft
grounding. With hydro-generators, the water acts as a grounding point, and with
turbogenerators the shaft can be grounded with a slip ring. However, the leakage
current can still occur if the bearing pedestal, which is isolated from the ground,
becomes grounded. This imposes shaft voltage on the oil-film of the bearing. The
current can break the insulation that the oil-film provides and thus it can cause
pitting and abrasion on the bearing face.
The measured shaft current is fed to the protection relay. The function compares
the current signal to the set alarm and operate levels. Operate time characteristics
are according to definite time.
Measurement device options
There are two different applicable shaft current measurement devices, the
Rogowski coil and the current transformer (CT). Both devices are installed around
the generator shaft. For both devices it is necessary to amplify the voltage signal.
The recommended measurement principles are depicted in
251
.
I
Figure 250: Current transformer measurement arrangement
REX640
Technical Manual
CT
Resistance
Protection functions
START_DUR , which indicates the
Alarm delay time , the ALARM
Figure 250
Amplifier
Protection relay
Reset
Figure
and
I>
437