ABB RELION REX640 Technical Manual page 106

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Basic functions
Fault
Fault indication
code
Internal Fault
-35
Conf. error, Slot
F
Internal Fault
-36
Conf. error, Slot
G
Internal Fault
-37
Conf. error, Slot
A1
Internal Fault
-40
Card error, Slot
C
Internal Fault
-41
Card error, Slot
E
Internal Fault
-42
Card error, Slot
A2
Internal Fault
-43
Card error, Slot
B
Internal Fault
-44
Card error, Slot
D
Internal Fault
-45
Card error, Slot
F
Internal Fault
-46
Card error, Slot
G
Internal Fault
-47
Card error, Slot
A1
Internal Fault
-62
640-Prod. Li-
cense error
106
Fast self-
Additional
recovery
information
attempt
Start up error: Card
No
in slot F is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
Start up error: Card
No
in slot G is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
Start up error: Card
No
in slot A1 is wrong
type, is missing,
does not belong
to original configu-
ration or card firm-
ware is faulty.
Card in slot C is
Yes
faulty.
Card in slot E is
Yes
faulty.
Card in slot A2 is
Yes
faulty.
Card in slot B is
Yes
faulty.
Card in slot D is
Yes
faulty.
Card in slot F is
Yes
faulty.
Card in slot G is
Yes
faulty.
Card in slot A1 is
Yes
faulty.
Runtime error:
No
Product license er-
ror, license file is
not found or is
wrong
Slow 10min
self-
recovery
Immediate
(# of
attempts)
IRF-mode
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
1MRS759142 F
Action in permanent fault
state
change the hardware mod-
ule in slot D.
Check that the card in slot
F is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot F.
Check that the card in slot
G is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot G.
Check that the card in slot
A1 is proper type and prop-
erly installed. Then restart
the relay. If does not then
recover by restarting, it
is hardware module failure
most likely in question. Ex-
change the hardware mod-
ule in slot A1.
Exchange the hardware
module in slot C.
Exchange the hardware
module in slot E.
Exchange the communica-
tion module in slot A2.
Exchange the hardware
module in slot B.
Exchange the hardware
module in slot D.
Exchange the hardware
module in slot F.
Exchange the hardware
module in slot G.
Exchange the hardware
module in slot A1.
If SW update under Modifi-
cation Sales has been car-
ried out, redo the update. If
not recovered, contact your
nearest ABB representative
to check the next possible
corrective action.