ABB RELION REX640 Technical Manual page 277

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Outputs ALARM and URES_ALARM indicate bad quality data of system measurements
for selected U3P and URES, respectively.
Outputs WARNING and URES_WARNING indicate questionable quality data of system
measurements for selected U3P and URES, respectively.
3.20.16.6
Signals
Table 262: VMSWI Input signals
Name
U3P1
U3P2
U3P3
U3P4
URES1
URES2
URES3
URES4
SWITCH_TO2
SWITCH_TO3
SWITCH_TO4
Table 263: VMSWI Output signals
Name
SOURCE1
SOURCE2
SOURCE3
SOURCE4
U3P
URES
ALARM
WARNING
REX640
Technical Manual
If the numbers of channels connected to U3P1...U3P4 and URES1...URES4
does not match with the number of connected SWITCH_TOx inputs, the
configuration of the function fails.
Depending on the connected U3P channels to the voltage switch,
Primary voltage settings between the source U3P must match.
the
Respectively, depending on the connected URES channels, the
voltage settings between the source URES must match. Setting validation
for the primary voltages fails unless they are all stored simultaneously to
the protection relay.
Type
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
Default
Description
-
Three-phase voltages
1
-
Three-phase voltages
2
-
Three-phase voltages
3
-
Three-phase voltages
4
-
Residual voltage 1
-
Residual voltage 2
-
Residual voltage 3
-
Residual voltage 4
0=False
Switch to source 2
0=False
Switch to source 3
0=False
Switch to source 4
Description
Selected voltage source is source 1
Selected voltage source is source 2
Selected voltage source is source 3
Selected voltage source is source 4
Three-phase voltages
Residual voltage
Alarm
Warning
Basic functions
Primary
277