Com1 Monitored Data; Com2 Settings - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Parameter
Values (Range)
4=RS232 with hand-
shake
Baudrate
1=300
2=600
3=1200
4=2400
5=4800
6=9600
7=19200
8=38400
9=57600
10=115200
3.1.25

COM1 Monitored data

Table 31: Monitored data
Name
Type
Characters received
INT32
Frames received
INT32
Frames discarded
INT32
Frames transmitted
INT32
CD lost
INT32
Collision
INT32
CTS Timeout
INT32
Transmission timeout
INT32
Parity errors
INT32
Overrun errors
INT32
Framing errors
INT32
Reset counters
BOOLEAN
3.1.26

COM2 Settings

Table 32: Non group settings
Parameter
Values (Range)
Serial mode
1=RS485 2Wire
2=RS485 4Wire
3=RS232 no hand-
shake
4=RS232 with hand-
shake
Fiber mode
0=No fiber
Table continues on the next page
REX640
Technical Manual
Unit
Step
Values (Range)
-1...2147483646
-1...2147483646
-1...2147483646
-1...2147483646
-1...2147483646
-1...2147483646
-1...2147483646
-1...2147483646
-1...2147483646
-1...2147483646
-1...2147483646
0=False
1=True
Unit
Step
Default
6=9600
Unit
Description
Characters received
Number of successfully
received frames
Number of discarded
frames
Number of transmitted
frames
CD lost
Collision
CTS Timeout
Transmission timeout
Number of parity errors
Number of overrun er-
rors
Number of framing er-
rors
Resets counters
Default
1=RS485 2Wire
0=No fiber
Basic functions
Description
Baudrate
Description
Serial mode
Fiber mode (light
ON/OFF = idle)
77

Advertisement

Table of Contents
loading