Configurable Logic Blocks; Minimum Pulse Timer - ABB RELION REX640 Technical Manual

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Table 194: T_I8_TO_I32 Output signals
Name
INT32_OUT
3.20

Configurable logic blocks

3.20.1

Minimum pulse timer

3.20.1.1
Minimum pulse timer, two channels TPGAPC (ANSI 62TP)
Identification
Function description
Minimum pulse timer, two channels TPGAPC
Function block
Figure 120: Function block
Functionality
The minimum pulse timer, two channels, function TPGAPC contains two
independent timers. The function has a settable pulse length (in milliseconds).
The timers are used for setting the minimum pulse length for example, the signal
outputs. Once the input is activated, the output is set for a specific duration using
the
Figure 121: A = Trip pulse is shorter than Pulse time setting, B = Trip pulse is longer
than Pulse time setting
REX640
Technical Manual
Type
INT32
Pulse time setting. Both timers use the same setting parameter.
Description
Integer output value
IEC 61850
IEC 60617
identification
identification
TP
Basic functions
ANSI/IEEE C37.2
device number
62TP
231