ABB RELION REX640 Technical Manual page 926

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
4.6.1.7
Signals
FRPFRQ Input signals
Table 883: FRPFRQ Input signals
Name
U3P
BLOCK
FRPFRQ Output signals
Table 884: FRPFRQ Output signals
Name
OPERATE
OPR_OFRQ
OPR_UFRQ
OPR_FRG
START
ST_OFRQ
ST_UFRQ
ST_FRG
4.6.1.8
FRPFRQ Settings
Table 885: FRPFRQ Group settings (Basic)
Parameter
Values (Range)
Operation mode
1=Freq<
2=Freq>
3=df/dt
4=Freq< + df/dt
5=Freq> + df/dt
6=Freq< OR df/dt
7=Freq> OR df/dt
Start value Freq>
0.9000...1.2000
Start value Freq<
0.8000...1.1000
Table continues on the next page
926
Type
SIGNAL
BOOLEAN
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
xFn
0.0001
xFn
0.0001
Default
Description
-
Three-phase voltages
0=False
Block signal for acti-
vating the blocking
mode
Description
Operate
Operate signal for overfre-
quency
Operate signal for underfre-
quency
Operate signal for frequency
gradient
Start
Start signal for overfrequency
Start signal for underfre-
quency
Start signal for frequency
gradient
Default
1=Freq<
1.0500
0.9500
1MRS759142 F
Description
Frequency protec-
tion operation
mode selection
Frequency start val-
ue overfrequency
Frequency start val-
ue underfrequency
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents