Basic functions
Parameter
Values (Range)
Amplitude Corr B
0.9000...1.1000
Amplitude Corr C
0.9000...1.1000
Angle Corr A
-8.0000...8.0000
Angle Corr B
-8.0000...8.0000
Angle Corr C
-8.0000...8.0000
Table 132: UTVTR Non group settings (Advanced)
Parameter
Values (Range)
Frequency adaptivi-
0=Disable
ty
1=Enable
2=Main frequency
source
3=Backup frequen-
cy source
Table 133: UTVTR Non group settings (Basic)
Parameter
Values (Range)
Primary voltage
0.100...800.000
Secondary voltage
57...240
Amplitude Corr
0.9000...1.1000
Angle correction
-8.0000...8.0000
Table 134: UTVTR Non group settings (Advanced)
Parameter
Values (Range)
Frequency adaptivi-
0=Disable
ty
1=Enable
202
Unit
Step
0.0001
0.0001
deg
0.0001
deg
0.0001
deg
0.0001
Unit
Step
Unit
Step
kV
0.001
V
1
0.0001
deg
0.0001
Unit
Step
1MRS759142 F
Default
Description
correction of an
external voltage
transformer
1.0000
Phase B Voltage
phasor magnitude
correction of an
external voltage
transformer
1.0000
Phase C Voltage
phasor magnitude
correction of an
external voltage
transformer
0.0000
Phase A Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
0.0000
Phase B Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
0.0000
Phase C Voltage
phasor angle cor-
rection of an exter-
nal voltage trans-
former
Default
Description
0=Disable
Frequency adaptivi-
ty selection
Default
Description
11.547
Primary voltage
100
Secondary voltage
1.0000
Amplitude correc-
tion
0.0000
Angle correction
factor
Default
Description
0=Disable
Frequency adaptivi-
ty selection
Technical Manual