ABB RELION REX640 Technical Manual page 794

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Figure 451: Operating characteristic for the stabilized stage of the generator
differential protection function
4.3.7.6
Application
The differential protection works on the principle of calculating the differential
current at the two ends of the winding, that is, the current entering the winding
is compared to the current exiting the winding. In case of any internal fault,
the currents entering and exiting the winding are different, which results in a
differential current, which is then used as a base for generating the operating
signal. Due to this principle, the differential protection does not trip during external
faults. However, it should be noted that interturn faults in the same phase are
usually not detected unless they developed into some other kind of fault.
The short circuit between the phases of the stator windings normally causes
high fault currents. The short circuit creates a risk of damages to the insulation,
windings and stator core. The high short circuit currents cause strong current forces
which can damage other components in the machine. The short circuit can also
initiate explosion and fire. When a short circuit occurs in a machine, there is a
damage that has to be repaired. The severity and the repair time depend on the
degree of damage, which is highly dependent on the fault time. The fast fault
clearance of this fault type is of greatest importance to limit the damages and the
economic loss.
To limit the damages in connection to the stator winding short circuits, the fault
clearance time must be as short as possible (instantaneous). The fault current
contributions from both the external power system (via the machine or the block
circuit breaker) and from the machine itself must be disconnected as fast as
possible.
794
1MRS759142 F
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents